Commissioning a closed heating circuit usually comes down to whatever's quickest on the day: top it up with a hose until the gauge looks right, rely on whatever safety valve came built into the boiler, and move on. Pressure drifts, nobody tops it up again until a zone goes cold, and a boiler trips on low pressure at the worst possible time.

There's a better way: fit the protection and make-up water components properly, as their own parts rather than hoping the boiler's own fittings cover everything. RBM and Zilmet between them cover safety relief, automatic filling, balancing and expansion for a closed heating circuit. This post uses the SmartFiller automatic filling valve as the reference point.

Safety Relief Valves: 351 vs 353

Both are controlled-rise safety relief valves for closed heating and cooling circuits, with a 15mm orifice and a brass body:

  • Series 351 - valve only, factory calibrated from 1.5 to 10 bar depending on size, in 1/2in or 3/4in.
  • Series 353 - the same valve with a dial pressure gauge fitted, so you can read system pressure and the relief setting at one connection. Calibrated 2 to 10 bar.

RBM's listings for both are explicit on a point worth flagging clearly: these are not AS 1357 temperature and pressure relief valves, and must not be fitted to a water heater or potable water supply. They're for closed heating and cooling circuits only. That's an easy mix-up if you're used to reaching for a T&P valve by habit - check which standard a relief valve is rated to before it goes on the job, not just whether it fits the thread.

One Fitting Instead of Three: Boiler Safety Unit

The Boiler Safety Unit (47.06.10) pre-assembles an automatic air vent, a 3 bar safety relief valve and a pressure gauge on a single 1in connection, rated to 75kW. It's a time saver on a straightforward boiler or heat pump install where you'd otherwise be fitting all three separately - though for a higher-capacity plant room, a standalone 353 relief valve sized for the load plus a separate vent still gives you more flexibility on settings.

Keeping the Circuit Topped Up: SmartFiller

The SmartFiller is a diaphragm-operated automatic filling valve. Set the fill pressure on the graduated calibration knob, and it tops the circuit up to that pressure automatically as needed, with a built-in check valve so mains water can't be pushed backward into the circuit. Adjustable range is 0.5 to 4 bar downstream, rated to 16 bar upstream.

That replaces the manual-hose-and-watch-the-gauge routine with something that just holds the setpoint on its own.

A Complete Make-Up Water Connection: Automatic Filling Kit

For a commercial HVAC job, the Automatic Filling Kit (RBMS-21-0006) bundles a SmartFiller, an Airterm inline deaerator, an isolation valve, a 4-way brass tee and a safety relief valve as one order - the parts list for a make-up water connection into a pressure vessel or system, rather than sourcing each fitting separately.

Balancing and Bypass

Two different jobs, easy to confuse:

  • BalanFlow - a static balancing valve with a turns-indicator knob and a memory stop, so once a zone or circuit is commissioned to the right flow, closing the valve for service and reopening it returns to the same setting. Tapped for pressure plugs (sold separately) for indirect flow measurement.
  • Adjustable By-Pass Valve - a differential-pressure bypass, set 0.1 to 0.7 bar, that opens to maintain minimum flow through the boiler or heat pump when zone valves close down and the main circuit would otherwise be starved.

BalanFlow sets how flow is distributed between zones at commissioning; the bypass valve protects the boiler or heat pump's minimum flow requirement as those zones open and close in normal operation. Most multi-zone jobs want both.

Expansion Vessels and Pressure Tanks: Don't Mix Them Up

Zilmet makes two vessel ranges that look similar but aren't interchangeable:

  • Cal-Pro - red, fixed-diaphragm expansion vessels for closed heating circuits only, 8L to 80L, absorbing the volume change as the system heats and cools so the safety relief valve doesn't lift every cycle. Not for potable water.
  • Ultra-Pro - blue, replaceable-bladder pressure tanks for pressure pumps, bore pumps and booster sets, 24L to 100L, 10 bar. A different application entirely - cutting pump cycling on a water supply, not managing heating expansion.

Small vessels up to 24L can go on the wall mount bracket (RBMS-21-0017) rather than sitting loose on the floor.

Buffer Tank Fit-Out and Dosing

The Buffer Tank Gauge Kit (RBMS-21-0012) supplies loose fittings for a buffer tank's instrument connections in one order: a thermometer, a 6 bar safety relief valve with gauge, a Megaluft HP air vent with its own check valve, and a drain isolation valve.

For dosing inhibitor into the system, the Chemical Dosing Pot (CDP-15) is a 15L stainless steel pot with valves and tundish, part-assembled, so treatment chemicals can go in without draining the circuit down.

Compliance: Closed Circuits Only

Every product in this post is built for closed-circuit hydronic heating and cooling - none of it is WaterMark-listed for drinking water, and the safety relief valves specifically are not a substitute for an AS 1357 temperature and pressure relief valve on a water heater. Keep heating-circuit and potable-water protection devices separate on the job, and install to the HVAC/heating standards and equipment manufacturer's instructions that apply.

Wrap-Up

A properly commissioned circuit needs relief, fill and expansion working together - a 353 safety relief valve sized to the boiler, a SmartFiller to hold pressure automatically, and a Cal-Pro vessel sized to the system volume. See the full range in our Hydronic Heating Accessories collection, plus our guides to magnetic filters and dirt separators and automatic air vents and deaerators for the rest of the circuit.

Frequently Asked Questions

Can I use an RBM safety relief valve instead of a water heater's T&P valve?

No. RBM's listings for both the 351 and 353 series state these are not AS 1357 temperature and pressure relief valves and must not be fitted to a water heater or potable water supply. They're for closed heating and cooling circuits only.

What's the difference between the Zilmet Cal-Pro and Ultra-Pro?

Cal-Pro is a fixed-diaphragm expansion vessel for closed heating circuits, absorbing volume change as the system heats and cools. Ultra-Pro is a replaceable-bladder pressure tank for pressure pumps and booster sets on a water supply. They're not interchangeable between those two applications.

What does a balancing valve do that a bypass valve doesn't?

A balancing valve (like BalanFlow) sets and holds the commissioned flow rate to a particular zone or circuit. A bypass valve opens automatically to maintain minimum flow through the boiler or heat pump when zone valves close, which a balancing valve doesn't do on its own.

Does the SmartFiller need a separate check valve?

No, it has one built in, stopping heating circuit water being pushed back into the mains supply.